ZY Cleanroom - specification text for tenders. Fill the brackets. Describes the item by function, not by brand. https://www.zycleanroom.com/products/cleanroom-ceilings/ CLEANROOM CEILINGS 1 GENERAL 1.1 Scope: supply [and install] the cleanroom ceiling to the reflected ceiling plan [ref, rev], including panels or grid, suspension, openings and seals. 1.2 Submittals: ceiling layout with module sizes and opening positions; suspension design with hanger positions; load statement (see 2.4); seal details at panel joints, wall junctions and every opening; [fire test report for the finished panel where required]. 1.3 The supplier states who supplies the hangers and who checks the structure above. 2 PRODUCTS 2.1 Type: [walkable sandwich panel ceiling / T-grid / I-grid steel / Z-grid concealed aluminium / FFU grid / thermal-break ceiling]. 2.2 Panels: [ ] mm thick, faces [colour-coated galvanized steel / stainless], core [rock wool / hollow MgO / aluminium honeycomb / paper honeycomb]. 2.3 Grid: module [ x ] mm, matched to the FFUs, filter housings and lights. 2.4 Loads (state as numbers): walking load [point N / kg; distributed kN/m2], fixed load of FFUs, lights and trays [ kg per module]; confirmed for the offered panel, span and supports. 2.5 Openings for lights, filters, FFUs and sprinklers cut at the factory where possible; every cut edge sealed. 2.6 Room face smooth, impervious and sealed against the space above. 2.7 Low-temperature rooms: profiles with a thermal break; room face to stay above the dew point at [ °C, % RH]. 3 EXECUTION 3.1 Hang from the structure at the approved hanger positions; seal each hanger point. 3.2 Seal panel joints, the wall-to-ceiling junction and every opening. 3.3 Walkable ceilings: mark walkways and access hatches; do not load before the load statement is approved.