ZY Cleanroom - specification text for tenders. Fill the brackets. Describes the item by function, not by brand. https://www.zycleanroom.com/products/ CLEANROOM WALL AND CEILING PANELS 1 GENERAL 1.1 Scope: supply [and install] metal-faced sandwich panels for cleanroom walls [and ceilings], with floor tracks, profiles, coving, trims, fixings and sealants, to drawings [ref, rev] and the panel schedule. 1.2 Submittals: dimensioned section drawing for each panel type (effective cover width, joint, both faces); numbered panel layout drawing; panel schedule with cut lengths and quantities; coating data for each face; fire test report for the panel assembly where a fire requirement is scheduled, stating laboratory, standard and the tested thickness and build-up; declared thermal value where insulation is scheduled; declared mass in kg/m2; installation instructions. 1.3 The supplier returns the layout drawing for approval before manufacture. Panels are cut to length and numbered to the approved drawing. 2 PRODUCTS 2.1 Panel: [ ] mm thick, effective cover width [ ] mm, lengths per schedule. 2.2 Core: [rock wool, density [ ] kg/m3 / MgO / PU / paper honeycomb / aluminium honeycomb]. Where a non-combustible core is scheduled, foam cores are not accepted. 2.3 Room-side face: [colour-coated galvanized steel / stainless steel grade ( )], [ ] mm, coating [PE / HDP / PVDF / anti-static], colour [ ]. 2.4 Corridor-side face: [as 2.3 / state separately]. 2.5 Joint: [centre aluminium connection / male-female / tongue-and-groove]; joints sealed so that the finished surface is continuous. 2.6 Surfaces: smooth, impervious and unbroken, without ledges or recesses that cannot be cleaned; face coating and sealants resistant to [cleaning and disinfectant agents, concentration, frequency]. 2.7 Tolerances: to EN 14509 [or state]: thickness, length, useful width, flatness and straightness. 2.8 Fire: [reaction-to-fire class ( ) / fire resistance ( ) for walls marked ( )], demonstrated by a test report for the panel assembly as supplied. A core description alone is not accepted as evidence. 2.9 Ceilings (where scheduled): [hung / self-supporting / walkable for a walking load of ( )], openings for FFUs, filters and lights per the reflected ceiling plan; load and deflection data for the assembly. 2.10 Accessories: floor track, H-connectors, corner posts, inner and outer curved coving at wall-floor, wall-wall and wall-ceiling junctions, door and window sections matched to the panel thickness. 3 EXECUTION 3.1 Sequence: floor track, wall panels, corners, ceiling, doors and windows, then lights, filters and penetrations, then final sealing. 3.2 Walls plumb, joints even and sealed on the room side; every penetration through a wall or ceiling sealed. 3.3 Door and window frames fixed flush with the panel face. 3.4 Check: joints, coving, seals and penetrations inspected and recorded before handover; [envelope leak test ( )].