Cleanroom pressure alarm: how to find the cause

A pressure alarm means the difference between two rooms has left its set limit, so air may now flow the wrong way. Do not override it: check the doors and the supply fan first, then filter loading, leakage paths and the sensor.

By ZY Cleanroom · Updated · Sources at the end of the page

First steps

Treat the alarm as real until the sensor is proved wrong. Annex 1 (para 4.16) says the warning signal should not be overridden without assessment, and a written procedure should say what to do.

FDA asks that all alarms are documented and deviations investigated. If the overpressure to an unclassified room falls below its minimum, FDA says the aseptic room's air quality should be restored and confirmed. Start from the limits.

SourcePressure difference
Annex 1, para 4.1410 Pa minimum between adjacent grades (guidance)
FDA, 2004At least 10 to 15 Pa between rooms of different class, doors closed (given as an example)
FDA, 2004At least 12.5 Pa from an aseptic room to an unclassified room (given as an example)
Cleanroom pressure alarm: how to find the cause

Find the cause

CheckWhat to look forBasis
DoorsDoor ajar, interlock fault, worn sealThe difference drops when a door opens (HTM 03-01, para 8.18)
Supply fan and AHUFan trip, lower speed, damper positionAnnex 1 asks for a warning on any air supply failure
FiltersLoaded filters raise resistance and cut airflowRead the filter gauge against its final resistance (HTM 03-01, paras 4.67 and 11.23)
Leakage pathsUnsealed ceiling or penetrations, changed door gapsAnnex 1, para 4.8; HTM 03-01, Appendix 4
Neighbouring roomsA change on the other side of the wall or doorA difference depends on both rooms
Sensor and tubingDrift, blocked tube, wrong zeroCross-check with a second calibrated gauge

Example: door leakage

Example only, from HTM 03-01 Appendix 4. A single door leaks 0.05 m³/s at 10 Pa, with gaps of 4 mm at the bottom and 3 mm at top and sides. A room with two such doors loses 0.10 m³/s, or 360 m³/h, before any other leak. Supply minus extract must cover that loss.

HTM notes that cold smoke seals cut door leakage. If the relief path is not sized for that, the room can whistle and air pressure can hold doors partly open. A seal change can shift the balance, so rebalance the air after it.

Stabilisers and containment rooms

HTM 03-01 (para 8.19) says pressure stabilisers set the room difference with the doors shut. They close when a door opens, which sends air through the doorway. Add them to the check list where they are fitted.

In a containment room the direction can be reversed. Annex 1 (para 4.14) allows modified pressures, including negative airlocks, for hazardous materials. Check that the alarm set point follows the intended direction.

What the design must provide

Annex 1 (para 4.16) asks for pressure indicators between rooms. Critical differences should be monitored and recorded continuously. Set points, criticality and any alarm delay belong in the contamination control strategy and must be justified.

HTM 03-01 (para 7.24) puts gauges beside the entry door, 1.5 m above the floor, with the normal range marked. FDA says alarms should catch an emerging low pressure before unclassified air enters.

After the fix

Annex 1 (para 4.32) includes the pressure difference between rooms in requalification. Record the cause and the action. If alarms repeat with no fault, review the design: supply capacity, door count and leakage paths.

Who approves the room

Your regulator or customer auditor judges the facility, not the contractor. The contractor builds to your room data sheet and supplies test data. To have a room list reviewed, send it to ZY Cleanroom, a cleanroom design-and-build contractor.

Questions

Common questions

What pressure difference should trigger the alarm?

The owner sets it. Annex 1 gives 10 Pa minimum between adjacent grades as guidance, and FDA gives at least 10 to 15 Pa. Set the alarm above the minimum you must keep.

Can I silence a pressure alarm?

Not without assessment. Annex 1 (para 4.16) says the signal should not be overridden without it, and a procedure should define the steps.

Why does the alarm sound when a door opens?

The difference drops when a door opens (HTM 03-01, para 8.18). Annex 1 says any alarm delay must be justified in the contamination control strategy.

How often should pressure be monitored?

Annex 1 asks for continuous monitoring and recording of critical differences. FDA asks for continuous monitoring through each shift, with frequent recording.

Related guides

Sources

Project enquiry

Send what you have

A room list, a floor plan or only the floor area is enough to start. After you submit, send drawings by email or WhatsApp.

We reply by email within one working day. We can sign an NDA before you send drawings.

WhatsApp +44 7962 561184 is our UK number for export enquiries. The factory is in Tianjin, China.

Email: [email protected]
WhatsApp: +44 7962 561184

Step 1 of 2

WhatsAppGet a budget range