ZY CleanroomTIANJIN · SINCE 2002 Get a budget range

Buyer guide

Modular operating theatres: scope, air and pressure standards

A modular operating theatre is a prefabricated, sealed room of wall and ceiling panels, doors, a ceiling air system and controls, installed inside a hospital shell. Air and pressure values come from the standard of the country where it is built: 20 total air changes per hour in the US standard, 22 or more in UK guidance, and a minimum 2.5 Pa positive pressure in India's NABH guidance.

By ZY Cleanroom · Updated · Sources at the end of the page

What is in scope

A typical package covers the panel envelope, floor finish, hermetic or sliding doors, a ceiling air diffuser with terminal filters, return grilles, a control panel and a pass-through hatch.

Agree in writing who supplies the air-handling unit, ducting, medical gases, surgical lights, pendants, isolated power and the link to the building management system. These items are often outside the panel contractor's scope.

Modular construction is a choice, not a rule. NABH's 2018 guidance says a modular operation theatre is not a mandatory requirement under any NABH programme, so the owner decides.

Modular operating theatres: scope, air and pressure standards

Air and pressure values by region

These are design values for the operating room itself. Check the current edition for your project.

StandardTotal air changesPressureAir speed at the tableTemperature and humidity
UK HTM 03-01 Part A, 202122 or more per hour25 Pa nominal (standard layout 1)0.2 to 0.3 m/s at 1 m above floor18 to 25 °C, set by staff
US ASHRAE/ASHE 170, Table 7-120 total, 4 outdoorPositive, no value givenNot set in the table20 to 24 °C, 20 to 60% RH
India NABH, 201820 minimum total, 4 fresh2.5 Pa minimum25 to 35 ft/min (0.13 to 0.18 m/s)21 ± 3 °C, 20 to 60% RH

Worked example: airflow for one theatre

HTM 03-01 standard layout 1 uses a 165 m³ theatre at 22 or more air changes per hour. The total supply is 1.01 m³/s, about 3,640 m³/h, made up of 0.73 m³/s primary air and 0.28 m³/s from the lay-up room. Size the AHU for your own room volume, not this example.

Other national classes

Germany's DIN 1946-4:2018 sorts rooms into room class I, with Ia and Ib, and room class II. China's GB 50333-2013 defines clean classes 5, 6, 7, 8 and 8.5 by particles of 0.5 µm and larger. Class 5 is above 350 and up to 3,500 particles per cubic metre.

Pressure and door design

UK guidance sets pressure room by room: theatre 25 Pa, scrub 25 Pa and lay-up preparation room 35 Pa (HTM 03-01 Part A, standard layout 1). A convertible suite can run the theatre at the same pressure as its corridor for infectious cases, with no air cascading out (para 8.125).

ASHRAE 170 Addendum y, approved 22 September 2026, requires a documented risk assessment before operational adjustments to space ventilation.

Put these in the room data sheet

State the filter grade. HTM 03-01 lists EPA E10, 85% at the most penetrating particle size, to E11, 95%, as typical for ultra-clean theatre terminals (Table 10). NABH asks for HEPA at 99.97% down to 0.3 µm and supply air at ISO 5 at rest.

State the airflow tolerance. HTM 03-01 gives the design airflow +10% and −0% as the normal commissioning tolerance and expects independent validation on the client's behalf (paras 11.29 and 11.16).

ASHRAE 170 lists MERV 16 as the minimum filter efficiency for operating rooms and does not allow air recirculation by room units. NABH asks for the filtered area to extend one foot beyond the table on all sides, and for 18 ± 2 °C in joint replacement theatres.

Who approves the room

Your health regulator or accreditation body judges the facility, not the contractor. The contractor builds to your room data sheet and supplies test results. The owner keeps the responsibility. To have a room list reviewed, send it to ZY Cleanroom, a cleanroom design-and-build contractor with its own panel factory in Tianjin, China.

Questions

Common questions

How many air changes per hour does an operating theatre need?

It depends on the country. ASHRAE 170 gives 20 total with 4 outdoor, HTM 03-01 gives 22 or more, and NABH gives 20 total with 4 fresh.

Does a modular theatre follow different air standards?

NABH says modular construction is optional. The national air and pressure values apply to the room, however it is built.

Should theatre pressure always be positive?

Usually. ASHRAE 170 lists operating rooms as positive. UK guidance allows a neutral-pressure theatre for infectious cases (HTM 03-01, para 8.125).

What air speed should the ceiling diffuser give?

HTM 03-01 gives 0.2 to 0.3 m/s at the operating position, 1 m above floor. NABH recommends 25 to 35 ft/min (0.13 to 0.18 m/s).

What are the zones of an operation theatre?

India's National Centre for Disease Control, citing the 2020 national infection control guidelines, lists four zones: unrestricted or clean, semi-restricted or sub-sterile, restricted or sterile, and disposal. The zones follow the level of sterility and cleanliness required. Names differ by country, so check your own health authority's standard.

What are the advantages of a modular operation theatre?

Walls, ceilings and doors are made off site and fitted as one system, so less wet work happens inside the hospital and joints can follow a drawing. Panels can also be rearranged later, although a changed layout needs retesting. The room must still meet the same air standard, so compare offers on test results.

Related guides

Sources

Project enquiry

Send what you have

A room list, a floor plan or only the floor area is enough to start. After you submit, send drawings by email or WhatsApp.

We reply by email within one working day. We can sign an NDA before you send drawings.