A hermetic cleanroom door is a door with seals made for low leakage when it is closed. It is used where the door has to hold room pressure, for example operating theatres, isolation rooms, the cleanest rooms of a pressure cascade and containment laboratories. Specify it by the pressure difference across the door and the leakage limit, not by the word "hermetic". We make hermetic doors in our own factory in Tianjin.

By ZY Cleanroom · Updated · Sources at the end of the page

Rooms where the door has to hold pressure

RoomPublished pressure valueSource
Operating theatre (UK)25 Pa; lay-up preparation room 35 PaHTM 03-01 Part A, standard layout 1
Operating theatre (India)At least 2.5 Pa to adjoining areasNABH, 2018
Isolation room, negative−5 Pa to the general area (UK); more negative than 2.5 Pa (US, new rooms)HTM 03-01 Table 4; CDC 2003
Bone marrow unit, positive+15 Pa to the corridorHTM 03-01
Pharmaceutical cleanroomAt least 10 Pa between adjacent grades (guidance value)EU GMP Annex 1, para 4.14
BSL-3 laboratoryNo pressure figure; gaps around doors must be sealableCDC and NIH BMBL, 6th edition

The pressure is held by the air system: supply minus extract equals what leaks out. Every closed door is a leak path, so the tighter the door, the less air the system needs to hold the same pressure.

How to Specify a Hermetic Door: When It Must Hold Room Pressure

How much air leaks through an ordinary door

UK HTM 03-01 Appendix 4 gives leakage through a closed single door with gaps of 4 mm at the bottom and 3 mm at the top and sides:

Pressure differenceLeakage, single doorPer hour
5 Pa0.03 m³/s108 m³/h
10 Pa0.05 m³/s180 m³/h
25 Pa0.07 m³/s252 m³/h

At 25 Pa, one ordinary door with those gaps lets out about 252 m³ of air an hour. In a small isolation room or airlock that is several air changes of offset the system must make up. The same appendix notes that factory-assembled steel-frame door sets with pre-hung leaves have effectively no closed-door leakage. Leakage grows with roughly the square root of pressure, so doubling the pressure takes about 1.4 times the air.

Specify the leakage, not the name

"Hermetic" and "airtight" are not test results. Write the requirement as numbers:

  • The pressure difference across the door and which side is higher.
  • The leakage limit the room design allows through the closed door, with units.
  • The test method and pressure. EN 12207:2016 grades internal pedestrian doorsets in classes A to D by air permeability; class D is 3 m³/(h·m²) at 100 Pa. If you use EN 12207, state the class and ask which table the report uses and the door area tested.
  • What is tested: the complete door with frame, seals, glazing and hardware, not the leaf or the seal alone.

Ask each supplier for leak test data for the door they offer.

A tight door still opens

When a hermetic door opens, the pressure difference across that doorway collapses. UK HTM 03-01 separates closed-door protection, where leakage flows from clean to less clean, from open-door protection, where airflow through the doorway replaces the lost pressure (para 8.18). A tight door improves the first. It does not replace the second.

  • Airlocks: EU GMP Annex 1 says airlock doors should not open at the same time (para 4.13). Airlocks to grades A and B should be interlocked; C and D need a visual or audible warning as a minimum.
  • Pressure relief: pressure stabilisers set the room pressure with the doors shut and close when a door opens, forcing air through the doorway (HTM 03-01 para 8.19). Without a relief path, air pressure can hold doors partly open (para 8.24).
  • Interlocks and escape: agree the emergency release for every interlocked door with the owner's fire safety lead.

Sliding or swing, and cleanability

Hermetic doors are made as sliding and as swing doors. A sliding door needs no swing arc, which suits operating theatres and corridors with trolley traffic. A swing door uses room pressure to help it shut when it opens towards the higher-pressure side. EU GMP Annex 1 asks that doors avoid recesses that cannot be cleaned and says sliding doors may be undesirable for that reason (para 4.6), so for a sliding door in a GMP room, ask how the track and the seal line are cleaned.

Whatever the type, the exposed surfaces should be smooth, impervious and unbroken (Annex 1 para 4.5) and tolerate repeated cleaning and disinfectants (para 4.7). A vision panel should sit flush on both faces of the leaf and is part of the tested door.

We make hermetic doors as sliding and as swing doors, manual or automatic. The operation and controls of each door are set on the door drawing.

Hermetic door schedule line

FieldWhat to write
Door mark and roomsD-05, theatre to corridor
PressureTheatre +25 Pa to corridor (from the HVAC design)
Leakage limit and testLimit in m³/h at the stated pressure; test method and class
Type and operationSliding or swing; manual or automatic; control and sensor positions
Clear passageWidth × height in the open position, mm
WallPanel thickness or measured masonry wall
Leaf finishFace material and the cleaning agents it must tolerate
Vision panelSize, position, flush on both faces
Interlock group and emergency releaseWhich doors are linked; how the door opens in an emergency
Fire ratingOnly if needed, for the complete tested assembly
DocumentsLeak test data for the offered door; drawings; installation instructions

Our hermetic doors

We make hermetic sliding and swing doors; see hermetic cleanroom doors.

Questions

Common questions

What is a hermetic door in a cleanroom?

A door with seals made for low leakage when closed, used where the door has to hold room pressure. Specify it by the pressure difference and the leakage limit, and ask for test data on the complete door.

What are hermetic doors for cleanrooms and operating theatres made of?

We make the leaf with stainless steel or colour-coated galvanized steel faces, or HPL faces, on steel, stainless steel or aluminium frames, with a flush double-glazed vision panel where needed. Choose the face by the disinfectants used and the knocks it takes from beds and trolleys. The seals are part of the door.

Do operating theatres need hermetic doors?

Operating theatre guidance sets the room pressure, for example 25 Pa for a UK theatre in HTM 03-01, not a door type. A hermetic door is one way to hold that pressure with less air. Sliding doors are common in theatres because they need no swing space.

What is the difference between a hermetic door and a standard cleanroom door?

Both have smooth, cleanable faces and flush frames. A hermetic door adds seals made to keep closed-door leakage low, and should come with leak test data at a stated pressure.

How is the airtightness of a cleanroom door measured?

By testing air permeability of the complete door at set pressures. EN 12207:2016 classes internal doorsets A to D; class D is 3 m³/(h·m²) at 100 Pa. Ask which method and pressure the report uses.

Does a hermetic door replace an airlock or interlock?

No. It reduces leakage while closed. When it opens, pressure across the doorway collapses, so airlocks, interlocks and open-door airflow are still needed.

Do you make hermetic doors for operating theatres?

Yes. We make hermetic sliding and swing doors, manual or automatic, for operating theatres, isolation rooms and cleanrooms, in our own factory in Tianjin, for panel walls and brick or block openings.

Related guides

Sources

Project enquiry

Send what you have

A room list, a floor plan or only the floor area is enough to start. After you submit, send drawings by email or WhatsApp.

We reply by email within one working day. We can sign an NDA before you send drawings.

WhatsApp +44 7962 561184 is our UK number for export enquiries. The factory is in Tianjin, China.

Fastest reply: message us on WhatsApp. Or use the form, and add your WhatsApp number so we can reply there.

Email: [email protected]
WhatsApp: +44 7962 561184

Step 1 of 2

Chat on WhatsAppGet a budget range