Buyer guide
Cleanroom and laboratory furniture: what to specify
Furniture in a cleanroom lab has to survive the room's cleaning agents, keep return air grilles clear, leave space to clean under and between units, and be in place before the at-rest test. Specify it from the room layout and equipment list, name the disinfectants you use, and cite the furniture standard that fits your lab. Furniture does not set the room's class; the class is confirmed by testing.
By ZY Cleanroom · Updated · Sources at the end of the page
The four requirements that come from the room
| Requirement | Why | Source |
|---|---|---|
| Materials minimise particle shedding and tolerate repeated cleaning, disinfectant and sporicidal agents | Furniture is cleaned with the room | EU GMP Annex 1 (2022) para 4.7 |
| Worktops are impervious to water and resistant to heat, organic solvents, acids, alkalis and other chemicals | Spills and decontamination | CDC/NIH BMBL 6th edition, Section IV, BSL-1 D-5 |
| Furniture supports the expected loads and uses | Analysers, centrifuges and incubators are heavy | BMBL 6th ed., BSL-1 D-5 |
| Spaces between benches, cabinets and equipment are accessible for cleaning | Dust and spills collect in gaps | BMBL 6th ed., BSL-1 D-4 |
BMBL also says chairs used for lab work are covered in a non-porous material that is easy to clean, and that carpets and rugs are not appropriate in labs. These are the biosafety level 1 items; BSL-2 builds on them.

Name the cleaning agents first
A worktop or finish that is fine with detergent may stain, swell or corrode under a sporicide. Annex 1 para 4.7 ties the material choice to the agents that are used. So the first line of a furniture specification is the list of agents, with concentrations and how often they are used.
Then ask every supplier the same questions for each material offered:
| Check | Ask for |
|---|---|
| Worktop | Chemical resistance results against your agent list; edge and joint sealing |
| Metal frames and cabinets | Material and finish; the steel grade if stainless; behaviour with chlorine-based agents if you use them |
| Joints and fixings | Exposed screw heads, open seams and hollow sections that liquid can enter |
| Castors and feet | Material, and whether the unit can be moved to clean under it |
| Shelves | Open wire or solid; how they are wiped |
Keep the answers in one table so the offers can be compared line by line.
Plan around air and equipment
Furniture affects the air system in two ways:
- Return air. Tall cabinets and wall benches can block low-level return grilles. Mark the grilles on the layout before placing benches, and keep a clear gap in front of each one.
- Heat. Incubators, centrifuges and analysers add heat that the air system has to remove. Fix the equipment list and positions first. Furniture goes around the equipment, not the other way round.
Clean benches, laminar flow hoods and biosafety cabinets are devices with their own airflow, not furniture. Specify them separately and leave the service space they need. See the guide on laminar flow hoods, clean benches and biosafety cabinets.
Furniture and the at-rest test
ISO 14644-1:2015 classifies a room in one of three occupancy states: as-built, at-rest or operational. At rest means the installation is complete, with equipment installed and operating as agreed, but no personnel present. Furniture is part of that installation. If it arrives after the at-rest test, the test was done on a different room. Put the furniture delivery before the at-rest test in the programme.
Which standard to cite
| Lab type | Standard to cite | What it covers |
|---|---|---|
| Higher education and research labs | EN 14056-1:2025 | General guidance for the design, selection, installation and handover of laboratory benches |
| School labs | EN 13150:2020 | Workbenches for educational labs: dimensions, safety and durability, with test methods |
| Fume cupboards | EN 14175 series | Fume cupboard types, tests on site and in type tests |
If the project follows a different national standard, cite that one instead. Check the edition in force before you write the reference into a tender.
A furniture schedule that suppliers can quote
Give each item a mark and one line in a schedule:
| Field | Example |
|---|---|
| Mark | LF-04 |
| Room and class | Cell culture, grade B background to a grade A cabinet |
| Item | Wall bench, closed base, no upper shelf |
| Size | L × D × H from the layout, mm |
| Worktop | Resistant to the agents listed in section 2 |
| Services | Power on a wall-mounted track, no water |
| Equipment on it | Name and weight of each item |
| Clearance | Gap to the return grille, mm |
| Drawing revision | B |
One quotation with the room
Laboratory furniture is part of the ZY Cleanroom product range. We supply it with the panels, doors, windows, pass boxes and clean benches for the same rooms in one quotation, and each item is inspected before shipping. Because it is quoted from the same layout and equipment list as the wall panels, service routes through the panels and the positions of sockets and pass boxes are planned once.
Questions
Common questions
What is cleanroom furniture?
Benches, cabinets, chairs, shelves and carts made for rooms with controlled particle levels and regular disinfection. They shed few particles, tolerate the cleaning agents and leave space to clean around them.
What worktop is best for a cleanroom lab?
The one that resists your cleaning agents and the chemicals used on that bench. Send the agent list and the work done on each bench, and ask for chemical resistance results for each worktop offered.
Can ordinary lab furniture be used in a cleanroom?
Only if it meets the room's needs: low shedding, tolerance of the disinfectants, no open seams that hold liquid, and space to clean under it. Check each item against Annex 1 para 4.7 and your agent list.
Does furniture affect the ISO class of a room?
It does not set the class, but it is in the room for the at-rest test, and it can block return air. Place it before the at-rest test and keep the grilles clear.
Should cleanroom chairs be upholstered?
BMBL says chairs used for lab work are covered with a non-porous material that is easy to clean. Fabric does not meet that.
Which standard covers laboratory benches?
EN 14056-1:2025 for higher education and research labs, and EN 13150:2020 for school labs. Fume cupboards are covered by the EN 14175 series.
Related guides
- What a cleanroom costs to run: energy, filters and testing
- How long does it take to build a cleanroom?
- Cleanroom contractor selection: steps, questions and evidence
- How to Import a Cleanroom from China
- Clean laboratories
- Turnkey cleanroom contractor
- Room list builder
Sources
Project enquiry
Send what you have
A room list, a floor plan or only the floor area is enough to start. After you submit, send drawings by email or WhatsApp.
We reply by email within one working day. We can sign an NDA before you send drawings.
WhatsApp +44 7962 561184 is our UK number for export enquiries. The factory is in Tianjin, China.
Fastest reply: message us on WhatsApp. Or use the form, and add your WhatsApp number so we can reply there.
Email: [email protected]
WhatsApp: +44 7962 561184