Softwall and portable cleanroom booths: fit and realistic class

A softwall or portable booth suits local, temporary or lower-risk work where no rule demands fixed walls, and it can claim only the class a particle count proves under ISO 14644-1. USP <797>, for one, separates a cleanroom suite from unclassified areas by fixed walls and doors, so a booth does not fit that case.

By ZY Cleanroom · Updated · Sources at the end of the page

When a booth fits

Check the rule before the product. The table lists four cases. FDA names carefully designed curtains as barriers that can segregate an aseptic line in suitable places. It does not name them as room walls.

CaseFitBasis
Cleanroom suite under USP <797>No: anteroom and buffer room are separated from unclassified areas by fixed walls and doorsUSP <797> 4.2.1
Barrier beside an aseptic filling lineCurtains and rigid plastic shields named as segregation barriersFDA aseptic guidance, 2004
Grade A and B areas under EU GMPCheck the curtain joints: surfaces smooth, impervious and unbroken; ceiling sealedAnnex 1 paras 4.5, 4.8
Local or temporary protection with no fixed-wall ruleThe owner decides, on a proved classNo standard names a wall type
Softwall and portable cleanroom booths: fit and realistic class

What class you can claim

A class is a particle count. ISO 14644-1 sets the limits and names no wall type. We found no standard or independent test data that assigns a class to softwall booths. Treat any class claim as unproven until it is counted.

The table shows the 0.5 µm limits and the air supply references. The USP <797> air changes apply to compounding rooms. They are not a rule for every booth. They show the scale of supply a classed room needs.

ISO classParticles at 0.5 µm and larger, per m³Air supply reference
ISO 53,520Unidirectional airflow; Annex 1 guidance 0.36 to 0.54 m/s at the working position
ISO 7352,000USP <797>: at least 30 total HEPA-filtered air changes per hour
ISO 83,520,000USP <797>: at least 20 total HEPA-filtered air changes per hour

Worked example: air supply for one booth

Assumed booth of 3 × 3 × 2.4 m is 21.6 m³. At 30 air changes per hour the supply is 21.6 × 30 = 648 m³/h. At 20 it is 432 m³/h. A fan filter unit that supplies an assumed 1,000 m³/h gives 1,000 ÷ 21.6 = 46 air changes per hour in the same booth, before any leakage.

Leakage and entry decide the result

Curtain gaps, an open skirt and door openings let outside air in. Annex 1 gives a minimum 10 Pa difference between adjacent rooms of different grade as a guidance value (para 4.14). Test whether the booth holds a pressure with the door closed and during entry.

FDA asks for airlocks between the entrance to an aseptic manufacturing area and the adjoining unclassified area. A booth entered straight from open floor has no such buffer. Ask how entry is handled.

Annex 1 para 4.32 sets requalification at no more than 6 months for grade A and B and 12 months for grade C and D. Ask which tests repeat after the booth is moved.

Curtain materials and fire

If the curtain material is thinner than 6 mm, ANSI/FM 4910-2013 sends it to the parallel panel test. It sets flame height at 1.83 m or less among five conditions. Ask for the test report of the curtain material. A material test does not approve the booth.

Put these in the data sheet

State the class and the room state, at rest or in operation. State the particle sizes to count, the count positions, the air supply and its velocity, the pressure target, the entry method, the curtain fire test and the retest after a move.

Who approves the room

Your regulator or customer auditor judges the facility. The supplier builds to your data sheet and supplies test results. The owner keeps the responsibility. To have a room list reviewed, send it to ZY Cleanroom, a cleanroom design-and-build contractor with its own panel factory in Tianjin, China.

Shipping container clean room: size, volume and what the box does not decide

A shipping container cleanroom is a standard steel container lined with panels and fitted with an air system. Start from the carrier's published inside sizes, because the lining and floor build-up take space. The table follows Maersk's equipment specification for its dry containers (undated; checked 1 November 2026). Sizes vary by container series, so confirm the unit you buy.

Assumed values: a 50 mm lining on the walls, floor and ceiling of a 20 ft standard container leaves 5.796 × 2.250 × 2.293 m, which is 29.9 m³. That is about 9% less than the carrier's 33 m³. At the 30 total air changes per hour that the USP <797> row in the table above lists for ISO 7 compounding rooms, the supply is 29.9 × 30 = 897 m³/h, or 598 m³/h at 20. An airlock, equipment and returns take more of this space.

The box does not decide the class. A panel-lined container has fixed walls, the point the table above raises against curtain booths, but the finished room must still meet the surface and sealing rules (EU GMP Annex 1 paras 4.5, 4.6 and 4.8) and show its class by particle count under ISO 14644-1. The door opening limits the largest item you can bring in after lining, so list large equipment first.

ContainerInside length × width × height (mm)Door opening width × height (mm)Carrier-stated volume
20 ft standard5,896 × 2,350 × 2,3932,350 × 2,27433 m³
40 ft standard12,032 × 2,350 × 2,3932,340 × 2,27467 m³
40 ft high12,032 × 2,350 × 2,6972,340 × 2,57776 m³

Questions

Common questions

What ISO class can a softwall booth reach?

No standard ties a class to a wall type. The class is the one a particle count proves under ISO 14644-1. Ask for a count report at your state of use.

Can a softwall booth meet USP <797>?

USP <797> asks that a cleanroom suite be separated from unclassified areas by fixed walls and doors, so a booth does not replace one.

How much air does a booth need?

It depends on the class and the process. USP <797> asks compounding rooms for at least 30 air changes per hour at ISO 7 and 20 at ISO 8.

Do portable booths need retesting?

Annex 1 sets requalification at no more than 6 months for grade A and B. Ask which tests repeat after a move.

Related guides

Sources

Project enquiry

Send what you have

A room list, a floor plan or only the floor area is enough to start. After you submit, send drawings by email or WhatsApp.

We reply by email within one working day. We can sign an NDA before you send drawings.

WhatsApp +44 7962 561184 is our UK number for export enquiries. The factory is in Tianjin, China.

Email: [email protected]
WhatsApp: +44 7962 561184

Step 1 of 2

WhatsAppGet a budget range