ZY CleanroomTIANJIN · SINCE 2002 Get a budget range

Buyer guide

Operating Theatre Doors: Types, Sizes and Specification

An operating theatre door has to hold the theatre's pressure, let a bed or trolley through, close by itself and stay cleanable. Most theatres use a hermetic sliding door, often automatic and hands-free, on the main bed entrance, and swing doors to the scrub, preparation and support rooms. The rule is not the same everywhere: Mexico's hospital standard requires double-swing doors with vision panels for the operating room. Dubai Health Authority guidance recommends a clear opening of at least 1400 × 2140 mm where beds pass in new patient areas. We make operating theatre doors in our own factory in Tianjin: hermetic sliding and swing doors, manual or automatic, with flush vision panels, for panel walls and brick or block openings.

By ZY Cleanroom · Updated · Sources at the end of the page

Which door goes where in an operating suite

OpeningUsual doorWhy
Theatre main entrance (bed and trolley)Hermetic sliding, automaticNo swing arc in the corridor; hands-free; holds pressure when closed
Scrub room to theatreHermetic sliding or swing, automatic or with push platesStaff with scrubbed hands
Preparation (lay-up) room to theatreSwing or sliding, self-closingRoom runs at higher pressure than the theatre in UK guidance
Anaesthetic roomSliding or swing, self-closingBed or trolley route
Dirty utility / disposalSwing, self-closingKept closed; lower pressure
Suite entrance from the hospitalAutomatic sliding or swing, self-closingRestricted access; frequent traffic

DHA guidance says automatic doors are useful where rapid, hands-free access is wanted, such as the entry to the operating unit, but are not mandatory. It lists operating-unit entry doors and airlocks among doors that should have self-closing devices, and says hold-open devices should not be fitted to doors of pressurised rooms.

Operating room with blue cleanroom wall panels, a laminar-flow ceiling, a flush door and coved corners
Operating room with blue cleanroom wall panels, a laminar-flow ceiling and coved corners
Operating Theatre Doors: Types, Sizes and Specification

Operating theatre door rules by country

Country or codeWhat it says about the theatre or its doors
United Kingdom, HTM 03-01 Part ATheatre 25 Pa, preparation room 35 Pa (standard layout 1); doors must let the air system hold these
UAE (Dubai), DHA Health Facility Guidelines Part CClear opening at least 1400 × 2140 mm where beds pass in new patient areas; self-closers on operating-unit entries; observation glass in operating and scrub room doors; sliding doors top-hung, no floor track; no pocket doors in operating rooms
India, NABH 2018At least 2.5 Pa against adjoining areas
Mexico, NOM-016-SSA3-2012Operating room doors double-swing with vision panels (6.6.2.2.4.3); doors and corridors wide enough for stretchers and equipment (6.6.9.1.2.12)
Other countriesUse the national health facility code named in the project brief

Ask your designer which code applies before choosing between sliding and swing doors: the same theatre can need a hermetic sliding door in one country and a double-swing door in another.

Operating theatre doors in Mexico (NOM-016-SSA3-2012)

NOM-016-SSA3-2012 sets the minimum infrastructure for Mexican hospitals. For the operating room it says:

ClauseRequirement
6.6.2.2.4Sanitary coves where walls meet each other and the floor, for cleaning
6.6.2.2.4.3Operating room doors double-swing, with vision panels
6.6.9.1.2.12Areas, accesses, corridors and doors wide enough for stretchers, equipment and staff to move easily

So for a Mexican operating room, specify double-swing (double-acting) doors with flush vision panels, self-closing, with smooth cleanable faces and seals to suit the theatre pressure. We make double-swing doors and flush double-glazed vision panels in our own factory. If the project brief also asks for a hermetic door, agree with the designer how it meets the double-swing rule before ordering.

Pressure in the theatre and what it does to the door

UK HTM 03-01 gives a nominal 25 Pa for the theatre and 35 Pa for the lay-up preparation room (standard layout 1); India's NABH guidance asks for at least 2.5 Pa against adjoining areas. With ordinary gaps of 4 mm at the bottom and 3 mm at the top and sides, a closed single door leaks about 0.07 m³/s at 25 Pa (HTM 03-01 Appendix 4). That is why the main theatre door is usually hermetic: it lets the air system hold the pressure with less air.

The pressure also pushes on the leaf: 25 Pa on a 1.0 × 2.1 m swing leaf is 52.5 N, so swing doors need closers and handles sized for it. When any door opens, the pressure across that doorway is lost, so the air system must also give open-door protection (HTM 03-01 para 8.18). See hermetic cleanroom doors.

Clear width for beds and trolleys

There is no single international size. Use the rules of the country where the hospital is built and the largest bed, trolley or equipment on the route.

Room or use (DHA guidance)Recommended minimum clear opening
Patient bedrooms, new areas (bed movement)1400 mm wide × 2140 mm high
Patient bedrooms, renovated areasNot less than 1200 mm wide × 2040 mm high
Rooms needing stretcher or wheelchair access900 mm wide
Rooms needing hoists or shower trolleys1000 mm wide

Write the clear opening in the door schedule, not the leaf size: on a sliding door the leaf overlaps the opening, and on a swing door the leaf thickness and hardware take some of the width. For unequal-leaf swing doors, the wide leaf is used daily and the second leaf opens for beds. See the door size and specification guide.

Sliding doors in theatres: keep the floor clean

DHA guidance says sliding doors should hang from a top track only, with no floor track, because floor tracks collect dust and are hard to clean; a small floor guide fixed to the frame is acceptable. It does not allow cavity (pocket) sliding doors in operating rooms because the cavity cannot be cleaned. EU GMP Annex 1 makes the same point for pharmaceutical cleanrooms (para 4.6). Our sliding doors are surface-mounted on the wall face and hang from a top track.

Vision panels, finishes and grounding

  • Vision panel: DHA guidance recommends observation glass in doors to operating and procedure rooms, scrub rooms and airlocks, and a cover that fully obscures the panel where lasers are used. Our door vision panels are double-glazed and sit flush in the leaf.
  • Faces: our leaves have colour-coated galvanized steel or stainless steel faces; HPL or resin-faced leaves are also available. Choose by the disinfectants used and the impact from beds and trolleys.
  • Metal leaves: DHA guidance notes that metal door leaves may hold static charge and need grounding in cardiac protected areas. Tell us if the theatre is a cardiac protected area, so the grounding is shown on the door drawing.
  • No grilles or undercuts: DHA guidance does not recommend door grilles or undercuts in pressurised isolation rooms; in a theatre, pressure relief is part of the air design, not the door.

Operating theatre door schedule line

FieldExample entry
Door mark and roomsD-OT1, theatre 1 to clean corridor
Type and operationHermetic sliding, single leaf, automatic
Leaf arrangementSingle sliding, bi-parting (two leaves opening from the centre) for wide bed openings, or double-swing where the code asks for it
Clear opening1400 × 2140 mm (from the local rule and the bed size)
PressureTheatre +25 Pa to corridor (from the HVAC design)
LeakageLimit and test pressure from the design; leak test data for the offered door
ActivationHands-free sensor, foot or elbow switch, push button; positions on the drawing
SafetyObstruction sensing, manual opening on power loss, emergency release
Vision panelFlush, double-glazed; cover if lasers are used
Leaf faceStainless steel or HPL; cleaning agents listed
InterlockWith the scrub room door, if the design asks for it
Wall50, 75 or 100 mm panel wall, or measured masonry opening
Fire ratingOnly if needed, for the complete tested door
Radiation shieldingOnly where X-ray is used in the theatre: lead equivalence from the radiation protection adviser; shielding continued in the frame and around the vision panel; evidence for the complete door

Our operating theatre doors

We make operating theatre doors in our own factory in Binhai, Tianjin: hermetic sliding and swing doors, manual or automatic, single, double and unequal leaf, with steel, stainless steel or aluminium frames for 50, 75 and 100 mm panel walls or measured brick and block openings. They are quoted from your door schedule with the theatre panels, so frames and openings are planned on one layout. You can see the door line on a live video tour before you order.

To start, chat on WhatsApp (+44 7962 561184) with the door schedule or the theatre layout, or send it through the enquiry form.

Questions

Common questions

What type of door is used in an operating theatre?

Usually a hermetic sliding door on the main bed entrance, often automatic and hands-free, and self-closing swing or sliding doors to the scrub, preparation and support rooms.

How wide should an operating theatre door be?

Wide enough for the largest bed or trolley, and at least what local rules require. Dubai Health Authority guidance recommends a minimum clear opening of 1400 × 2140 mm for bed movement in new patient areas.

Do operating theatre doors need to be airtight?

They need to help hold the theatre pressure, for example 25 Pa in UK guidance. An ordinary door leaks noticeably at that pressure, so the main theatre door is usually hermetic. Ask for leak test data on the offered door.

Should theatre doors be automatic?

Automatic doors suit hands-free entry and are common at theatre and operating-unit entrances, but DHA guidance says they are not mandatory. Agree how the door opens on power loss and in an emergency.

Can a sliding theatre door have a floor track?

DHA guidance says no: use a top track only, with at most a small floor guide, because floor tracks collect dirt.

Do you make operating theatre doors?

Yes. We make hermetic sliding and swing doors, manual or automatic, in our own factory in Tianjin.

Are operating theatre doors sliding or swing?

Mostly hermetic sliding, often automatic, in the UK and the Gulf. Mexico's NOM-016-SSA3-2012 requires double-swing doors with vision panels for the operating room. We make both, so follow the code of the country where the hospital is built.

Do operating theatre doors need lead lining?

Only where X-ray equipment is used in the theatre. The radiation protection adviser sets the lead equivalence, and the shielding must continue through the frame and around any vision panel. State it in the door schedule.

What types of operating theatre doors are there?

Hermetic sliding doors (single or bi-parting, manual or automatic), double-swing doors, and self-closing swing doors for scrub, preparation and support rooms. The country's code and the theatre pressure decide which one.

What does the Mexican NOM-016 say about operating room doors?

Clause 6.6.2.2.4.3 of NOM-016-SSA3-2012 requires operating room doors to be double-swing with vision panels. Clause 6.6.9.1.2.12 asks for doors wide enough for stretchers and equipment.

Related guides

Sources

Project enquiry

Send what you have

A room list, a floor plan or only the floor area is enough to start. After you submit, send drawings by email or WhatsApp.

We reply by email within one working day. We can sign an NDA before you send drawings.

WhatsApp +44 7962 561184 is our UK number for export enquiries. The factory is in Tianjin, China.

Fastest reply: message us on WhatsApp. Or use the form, and add your WhatsApp number so we can reply there.

Email: [email protected]
WhatsApp: +44 7962 561184

Step 1 of 2

Chat on WhatsAppGet a budget range